With lightning season approaching, have you properly selected your cabinet SPD? Improper SPD specification is worse than no installation at all. Save these four core selection rules.
![]()
4P SPD (full protection for L1/L2/L3/N) for TN‑S system; 3+1 configuration for TT system with independent MOV for neutral conductor. Wrong system matching renders SPD installation ineffective.
Uc (maximum continuous operating voltage) ≥ 1.1* nominal system voltage. For 220V grid, Uc ≥242V; 275V or 385V rated Uc is recommended for safety. Low Uc causes continuous SPD degradation under normal grid voltage, leading to thermal breakdown and fire hazards.
Three‑stage coordinated protection is mandatory; standalone terminal SPD lacks front surge interception.
SPD is a consumable degraded after repeated lightning surges. Products without visual status window (green→red) and remote alarm contact cannot alert users to component failure; include these two items in acceptance checklist.
Proper specification brings real surge protection; blind installation provides false safety.